Dec 13 – 14, 2025 HYBRID
Erzurum, Turkiye
Europe/Istanbul timezone

Effect of Using a Vertical Heat Exchanger on Performance in a Vapor Compressıon Heat Pump Using R417a Gas as an Alternatıve to R22

Dec 13, 2025, 4:00 PM
15m
D/1-5 - Hall 5 (Campus VSTS)

D/1-5 - Hall 5

Campus VSTS

20
Oral Presentation Mechanical Engineering: Energy and Thermodynamics Mechanical Sciences

Speaker

Fadime Şimşek (Atatürk Üniversitesi)

Description

In this study, a vertical shell-type heat exchanger was used as the superheating-cooling unit in a vapor-compression heat pump. R417A gas was selected as the refrigerant, requiring no additional modifications to the system. The ambient temperatures of the condensers and evaporators used in the system were 22°C and 15°C, respectively, and the airflow velocities were 3.7 m/s and 4.6 m/s, respectively. After the system stabilized, the calculated COP values ​​from the obtained data were examined. It was observed that using a vertical heat exchanger with a 6 mm finned spaced evaporator increased system performance by 16.43% compared to using a vertical heat exchanger with an 8 mm finned spaced evaporator.

Keywords R417A, Shell Type Heat Exchanger, COP

Author

Fadime Şimşek (Atatürk Üniversitesi)

Presentation materials

There are no materials yet.